Miniature Plug-in relay - HARMONY RXM 2 C/O 24 V DC 12 A
RXM2AB1BD
RXM miniature relays are part of Harmony Electromechanical Relays. This is a plug in relay to be mounted on a RXZE socket. It is a 2 C/O relay with current rating of 12A, control circuit voltage of 24 V DC. It also offers one-step loackable test button and mechanical indicator for contact status. The testbutton is activated momentarily by pushing the blue pushbutton on the front and locked by flipping up the green part. The mechanical indicator is next to the testbutton, where an orange flag indicates the relay contact status. Workablity for hard-wired logic automated systems to complement the functions of industrial progammable logic controllers (PLCs). Its design is fit for industrial machines, packaging, textile, HVAC, automation control panels, low/medium voltage switchgear, motor controls, PLC Interfaces, power supplies, building or medical equipment, lighting controls. This product conforms to international standard and certifications like IEC, CE, UL, CSA, EAC, Lloyd's, RoHS and REACH. RXM Relay should be used with a RXZE socket (screw clamp, screw connector, push-in terminal). To protect against vibrations, plastic/metal clamp can be added to the socket. Protection modules and marking legend are also available. It is sold in lots of 10 and reference includes relay only. The RXM plug-in relays are a series of industrial plug-in relays designed for both simple and complex automation systems and available with 2 CO (12A), 3 CO (10A), 4 CO (6A) contacts, 4 CO (3A) low level contacts.
Main
Range of product: Harmony Electromechanical Relays
Series name: RXM series
Product or component type: Plug-in relay
Relay type: Miniature relay
Contacts type and composition: 2 C/O
Status LED: Without
Control type: Lockable test button
[Uc] control circuit voltage: 24 V DC
[Ithe] conventional enclosed thermal current: 12 A
Continuous output current: 10 A
Complementary
[Uimp] rated impulse withstand voltage: 4 kV during 1.2/50 µs
[Ie] rated operational current:
12 A at 28 V (DC) NO conforming to IEC
12 A at 250 V (AC) NO conforming to IEC
6 A at 28 V (DC) NC conforming to IEC
6 A at 250 V (AC) NC conforming to IEC
12 A at 28 V (DC) conforming to UL
12 A at 277 V (AC) conforming to UL
Minimum switching capacity: 170 mW at 10 mA, 17 V
Electrical durability: 100000 cycles for resistive load
Rated operational voltage limits: 19.2...26.4 V DC
[Ui] rated insulation voltage:
250 V conforming to IEC
300 V conforming to CSA
300 V conforming to UL
Maximum switching voltage: 250 V conforming to IEC
Drop-out voltage threshold: >= 0.1 Uc
Load current:
12 A at 250 V AC
12 A at 28 V DC
Operating time: 20 ms
Maximum switching capacity: 3000 VA/336 W
Average resistance: 650 Ohm at 20 °C +/- 10 %
Average coil consumption: 0.9 W
Mechanical durability: 10000000 cycles
Safety reliability data: B10d = 100000
Operating rate:
<= 1200 cycles/hour under load
<= 18000 cycles/hour no-load
Utilisation coefficient: 20 %
Reset time: 20 ms
Dielectric strength:
1300 V AC between contacts with micro disconnection
2000 V AC between coil and contact with basic insulation
2000 V AC between poles with basic insulation
Compatibility code: RXM
Protection category: RT I
Pollution degree: 3
Operating position: Any position
Test levels: Level A group mounting
Device presentation: Complete product
Contacts material: AgNi
Shape of pin: Flat (faston type)
Net weight: 0.037 kg
Environment
Ambient air temperature for operation: -40…55 °C
IP degree of protection: IP40 conforming to IEC 60529
Standards:
CSA C22.2 No 14
UL 508
IEC 61810-1
Product certifications:
UL
Lloyd's
CE
CSA
GOST
IECEE CB Scheme
Ambient air temperature for storage: -40…85 °C
Vibration resistance:
3 gn, amplitude = +/- 1 mm (f = 10…150 Hz) 5 cycles in operation
5 gn, amplitude = +/- 1 mm (f = 10…150 Hz) 5 cycles not operating
Shock resistance:
10 gn for in operation
30 gn for not operating
Packing Units
Package 1
Unit Type of Package: PCE
Number of Units: 1
Package Height: 4.800 cm
Package Width: 2.100 cm
Package Length: 2.700 cm
Package Weight: 36.000 g
Package 2
Unit Type of Package: BB1
Number of Units: 10
Package Height: 3.000 cm
Package Width: 10.200 cm
Package Length: 12.500 cm
Package Weight: 387.000 g
Package 3
Unit Type of Package: S02
Number of Units: 240
Package Height: 15.000 cm
Package Width: 30.000 cm
Package Length: 40.000 cm
Package Weight: 9.806 kg
Dimensions Drawings

Pin Side View

Connections and Schema
Wiring Diagram

Symbols shown in blue correspond to Nema marking.
Performance Curves
Electrical Durability of Contacts
Durability (inductive load) = durability (resistive load) x reduction coefficient.
Resistive AC load

X Switching capacity (kVA)
Y Durability (Number of operating cycles)
A RXM2AB•••
B RXM3AB•••
C RXM4ΑΒ•••
D RXM4GΒ•••
Reduction coefficient for inductive AC load (depending on power factor cos ϕ)

Y Reduction coefficient (A)
Maximum switching capacity on resistive DC load

X Voltage DC
Y Current DC
A RXM2AB•••
B RXM3AB•••
C RXM4ΑΒ•••
D RXM4GΒ•••
Note : These are typical curves, actual durability depends on load, environment, duty cycle, etc.
For inductive load, to increase relay life cycles, please add a proper load protection circuit (eg: RC protection/Varistor/free Wheeling diode -DC load only- ).
For low level loads (below 10mA), we recommend to use RXM*GB series with bifurcated contacts relays instead.
Coil Operating Range
DC Coil Operating Range VS Ambient Temperature

X : Ambient temperature (°C)
Y : DC Coil voltage (U/Uc)
(1) : Permitted operating range area
规格
59, Jalan Hijauan Hills 2, Hijauan Hills, 14200 Simpang Ampat, Pulau Pinang, Malaysia.
微信
60178053811