Easy9 Residual Current Circuit Breaker - 4P - 40A - 100 mA - AC type - 400 V EZ9R56440
This product is a Easy9 residual current circuit breaker (RCCB). It is a 4P circuit breaker with 40A In rated current, a sensitivity of 100mA with a AC type protection class. This product protects against electrical shock by indirect contact and fire hazards. It also has protection against fire hazards due to persistent earth fault current. This product has a positive contact indications with fault tripping indication on the front panel by the position of the handle (0-I engraved). This is dedicated for residential and small commercial buildings market segment. This product is compliant with IEC 61008-1 standard. The (Im/IΔm) rated breaking and making short circuit capacity is 500A. The (Inc/IΔc) conditional rated short circuit current is 6000A. The mechanical endurance is going up to 5000 cycles and electrical endurance going up to 2000 cycles. The Ue operational voltage is 400VAC. The Ui rated insulation voltage is 440VAC. The Uimp rated impulse withstand voltage is 4kV. The frequency is 50Hz or 60Hz. It is DIN rail mountable. The width in 9mm pitches is 8. The product color is light grey (RAL7035). The dimensions are (W) 72mm x (H) 82mm x (D) 72mm. It has an IP20 degree of protection (as per IEC/EN 60529 standard) and becomes IP40 once in modular enclosure. The operating temperature is from -5°C to 60°C. The storage temperature is from -40°C to 85°C.
Main Characteristics
Range of product: Easy9
Product or component type: Residual current circuit breaker (RCCB)
Device short name: Easy9 RCCB
Poles: 4P
Neutral position: Left
Rated current ([In]): 40 A
Network type: AC
Network frequency: 50/60 Hz
Rated operational voltage ([Ue]): 400 V AC 50/60 Hz
Earth-leakage sensitivity: 100 mA
Earth-leakage protection time delay: Instantaneous
Earth-leakage protection class: Type AC
Residual current tripping technology: Voltage independent
Rated breaking and making capacity: 500 A
Rated conditional short-circuit current: Easy9 MCB: 6000 A 40 A
Rated insulation voltage ([Ui]): 440 V AC
Rated impulse withstand voltage ([Uimp]): 4 kV
Surge current: 250 A
Complementary Specifications
Device location in system: Outgoer
Control type: Toggle
Contact position indicator: Yes
Mounting mode: Clip-on
Mounting support: DIN rail
Comb busbar and distribution block compatibility: Top: YES
Connection pitch: 18 mm between phases (9 mm pitches: 8)
Durability:
Mechanical: 5,000 cycles
Electrical: AC: 2,000 cycles at 400 V AC 50/60 Hz
Terminals & Connections:
Tunnel type terminal (top or bottom) for 1…35 mm² rigid cables
Tunnel type terminal (top or bottom) for 1…25 mm² flexible cables