联络我们
数量 现货
已选择:
已选择:
EasyPact TVS contactor 3P (3 NO) - AC-3 - <= 440 V 9A - 240 V AC coil
LC1E0910U5
Easy TeSys Control contactor 3 poles for motor applications up to 9A 4kW@440V. It provides a 240V 50Hz AC coil, 1NO built-in auxiliary contacts, power and control connections by screw clamp terminals. 45mm width for standard operating rates up to 1800 cycles per hour. It procures standard reliability and durability with 1.4 Mcycles electrical durability AC-3 and 10 Mcycles mechanical durability. It can cover -5°C to 55°C working temperature and mounted by DIN-rail, No derating up to 3000m altitude. Multi-standards certified (IEC, CCC, EAC) and Environmental compliant (RoHs/Reach).
Main Characteristics
Range of product: Easy TeSys
Range product name: Easy TeSys Control
Product or component type: Contactor
Device short name: LC1E
Contactor application: Motor control, Resistive load
Utilisation category: AC-3, AC-3e, AC-1
Poles description: 3P (with 3 NO pole contact composition)
Rated operational voltage ([Ue]): Power circuit: image V AC 50/60 Hz
Rated operational current ([Ie]):
9 A (at image °C) at image V AC AC-3 / AC-3e for power circuit
25 A (at image °C) at image V AC AC-1 for power circuit
Control circuit voltage ([Uc]): 240 V AC 50 Hz
Complementary Specifications & Ratings
Motor power:
2.2 kW at 220/230 V AC 50/60 Hz
4 kW at 380/400, 415/440, 500, and 660/690 V AC 50/60 Hz
5.5 kW at 660...690 V AC 50/60 Hz
Thermal & Short-Time Current:
Conventional free air thermal current ([Ith]): 25 A (at 55 °C) for power circuit
Rated making capacity (Irms): 117 A at 440 V AC (IEC 60947-4-1)
Rated breaking capacity: 76.5 A at 440 V for power circuit (IEC 60947)
Short-time withstand current ([Icw]): 105 A (10 s), 61 A (60 s), 30 A (600 s) at 40 °C
Voltages & Insulation:
Rated insulation voltage ([Ui]): 690 V (IEC 60947-4-1)
Rated impulse withstand voltage ([Uimp]): 6 kV
Overvoltage category / Pollution degree: III / 3
Durability & Operating Rates:
Mechanical durability: 10,000,000 cycles
Electrical durability: 1,400,000 cycles (AC-3); 150,000 cycles (AC-1)
Maximum operating rate: 1,800 cyc/h at 60 °C
Control Circuit & Power Consumption:
Inrush power: 95 VA at 50/60 Hz (image 0.75 at 20 °C)
Hold-in power: 8.3 VA at 50 Hz / 8.5 VA at 60 Hz (image 0.3 at 20 °C)
Operating time: 12...22 ms closing / 4...19 ms opening
Auxiliary Contacts: 1 NO configuration, minimum switching voltage 17 V, minimum switching current 5 mA
Mounting & Dimensions:
Mounting support: DIN rail, Plate
Dimensions: Height 74 mm, Width 45 mm, Depth 80 mm
Net weight: 0.3 kg
Environment & Compliance
Standards: EN/IEC 60947 series, GB/T 14048 series, IS/IEC 60947 series, EN/IEC 60335-1
Product certifications: CB Scheme, CCC, CE, EAC, BIS
Degree of protection: IP2X (IEC 60529)
Ambient air temperature:
Operation: -5…55 °C (at Uc) / -20…70 °C
Storage: -60…80 °C
Operating altitude: 3000 m without derating
Contractual warranty: 18 months