This Multi9 C60SP is a low voltage miniature circuit breaker (MCB). It is a 2P circuit breaker with 2 protected poles, 2A rated current and D tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard and 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Its width is 4 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 36mm x (H) 81mm x (D) 72mm. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
Main Characteristics
Range of product: Multi9
Product name: Multi9 C60
Product or component type: Miniature circuit-breaker
Device short name: C60SP
Device application: Distribution
Poles description: 2P (2 protected poles)
Rated current ([In]): 2 A at 25 °C (conforming to EN/IEC 60947-2)
Network type: AC / DC
Trip unit technology: Thermal-magnetic
Curve code: D
Standards: EN/IEC 60947-2, GB/T 14048.2, UL 1077, CSA C22.2 No 235
Product certifications: IEC, CCC, UR, CSA
Breaking Capacities & Performance
Breaking Capacities (AIR / Icu):
14 kA AIR at 240 V AC (UL 1077 / CSA C22.2 No 235)
10 kA AIR at 480Y/277 V AC (UL 1077 / CSA C22.2 No 235)
10 kA AIR at 125 V DC (UL 1077 / CSA C22.2 No 235)
20 kA Icu at 240 V AC (EN/IEC 60947-2 / GB/T 14048.2)
10 kA Icu at 415 V AC (EN/IEC 60947-2 / GB/T 14048.2)
6 kA Icu at 440 V AC (EN/IEC 60947-2 / GB/T 14048.2)
Rated Service Breaking Capacity ([Ics]):
15 kA (75%) at 240 V AC
7.5 kA (75%) at 415 V AC
4.5 kA (75%) at 440 V AC
Magnetic Tripping Limit: 12 x In +/- 20% AC / 17 x In +/- 20% DC
Insulation & Voltage Ratings:
Rated operational voltage ([Ue]): 240 V, 415 V, 440 V AC (50/60 Hz)
Rated insulation voltage ([Ui]): 500 V AC
Rated impulse withstand voltage ([Uimp]): 6 kV
Complementary Specifications
Control type: Toggle
Local signalling / Indication: ON/OFF indication, Contact position indicator (Yes)
Mounting mode: Clip-on on DIN rail
Dimensions & Pitch:
9 mm pitches: 4
Height: 81 mm
Width: 36 mm
Depth: 72 mm
Colour: Grey
Durability:
Mechanical: 20,000 cycles
Electrical: 10,000 cycles
Connections & Terminals:
Tunnel type terminals (top or bottom) for rigid (1…25 mm² / 18…8 AWG) and flexible/ferrule (1…16 mm² / 18…8 AWG)
Wire stripping length: 14 mm
Tightening torque: 2.5 N.m
Provision for padlocking: Padlockable
Environment & Compliance
Degree of protection: IP20 / IP40 (in modular enclosure)
Pollution degree: 3
Tropicalisation: 2
Relative humidity: 95% at 55 °C
Operating altitude: 0...2000 m