Schneider Acti9 2P 40A Residual Current Circuit Breaker A9R12240



Acti 9 iID - RCCB - 2P - 40A - 100mA - type AC
A9R12240


This Acti9 iID is a modular and reliable residual current circuit breaker (RCCB). It is a 2P circuit breaker with 40A In rated current, a sensitivity of 100mA with a AC type protection class. This product protects against electrical shock by indirect contact and fire hazards. It performs the function of disconnection of electrical circuits in case of earth fault. Its unique Visitrip indicator reduces intervention time by showing the faulty device with a mechanical indicator on front face. This product also has a VisiSafe window with a green strip on the toggle indicating full opening of the poles allowing downstream maintenance This product is compliant with EN/IEC 61008-1 standard. The (Im/IΔm) rated breaking and making short circuit capacity is 1500A. The (Inc/IΔc) conditional rated short circuit current is 10kA. The mechanical endurance is going up to 20000 cycles and electrical endurance going up to 15000 cycles. The Ue operational voltage is 220VAC to 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The frequency is 50Hz or 60Hz. It is DIN rail mountable. The width in 9mm pitches is 4. The product colour is white (RAL9003). The dimensions are (W) 36mm x (H) 91mm x (D) 73.5mm. The weight is 0.21kg. It has an IP20 degree of protection (as per IEC/EN 60529 standard) and becomes IP40 once in modular enclosure. The operating temperature is from -5°C to 60°C. The storage temperature is from -40°C to 85°C.

Main Characteristics
  • Range of product: Acti9
  • Product name: Acti9 iID
  • Product or component type: Residual current circuit breaker (RCCB)
  • Device short name: iID
  • Poles description: 2P
  • Neutral position: Left
  • Rated current ([In]): 40 A
  • Network type: AC
  • Earth-leakage sensitivity: 100 mA
  • Earth-leakage protection time delay: Instantaneous
  • Earth-leakage protection class: Type AC
 
Complementary Specifications & Ratings
  • Device location in system: Outgoer
  • Network frequency: 50/60 Hz
  • Rated operational voltage ([Ue]): 230...240 V AC 50/60 Hz
  • Residual current tripping technology: Voltage independent
  • Capacities:
    • Rated breaking and making capacity: Idm 1500 A / Im 1500 A
    • Rated conditional short-circuit current: 10 kA
  • Insulation & Impulse Voltages:
    • Rated insulation voltage ([Ui]): 500 V AC 50/60 Hz
    • Rated impulse withstand voltage ([Uimp]): 6 kV
  • Control & Signalling:
    • Control type: Toggle
    • Contact position indicator: Yes
  • Mounting & Dimensions:
    • Mounting mode: Clip-on on 35 mm DIN rail
    • 9 mm pitches: 4
    • Height: 85 mm, Width: 36 mm, Depth: 69 mm, Embedding depth: 44 mm
    • Net weight: 210 g
    • Colour: White (RAL 9003)
  • Durability & Locking:
    • Mechanical durability: 20,000 cycles
    • Electrical durability: 15,000 cycles
    • Locking options: Padlocking device
  • Terminals & Connections:
    • Single terminal (top or bottom) for 1…35 mm² rigid cables
    • Single terminal (top or bottom) for 1…25 mm² flexible or flexible with ferrule cables
    • Wire stripping length: 14 mm
    • Tightening torque: 3.5 N.m (top or bottom)
 
Environment & Compliance
  • Standards: EN/IEC 61008-1, EN/IEC 61008-2-1
  • Product certifications: EAC
  • IP degree of protection: IP20 / IP40 (in modular enclosure)
  • Pollution degree: 3
  • Electromagnetic compatibility: 8/20 µs impulse withstand, 250 A
  • Ambient air temperature:
    • Operation: -5…60 °C
    • Storage: -40…85 °C
  • Contractual warranty: 18 months