Schneider GV2 4A Circuit Breaker Thermal-Magnetic GV2ME08



TeSys GV2-Circuit breaker-thermal-magnetic - 2.5...4 A - screw clamp terminals
GV2ME08

TeSys GV motor circuit breaker, 3 poles (3P), 4A/690V, for 3-phase motor applications 1.1-1.5kW@400V. It provides a thermal-magnetic protection with a thermal setting range 2.5-4A, magnetic tripping at 13xIn, high breaking capacity Icu 100kA@400V. Connection by screw clamp terminals. Start-stop control by push-button guaranteed for 100 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX).
Main

  • Range: TeSys Deca

  • Product name: TeSys GV2

  • Product or component type: Motor circuit breaker

  • Device short name: GV2ME

  • Device application: Motor protection

  • Trip unit technology: Thermal-magnetic

Complementary

  • Poles description: 3P

  • Network type: AC

  • Utilisation category:

    • Category A conforming to IEC 60947-2

    • AC-3 conforming to IEC 60947-4-1

    • AC-3e conforming to IEC 60947-4-1

  • Network frequency: 50/60 Hz conforming to IEC 60947-2

  • Motor power kW:

    • 1.1 kW at 400/415 V AC 50/60 Hz

    • 1.5 kW at 400/415 V AC 50/60 Hz

    • 1.5 kW at 500 V AC 50/60 Hz

    • 2.2 kW at 500 V AC 50/60 Hz

    • 3 kW at 690 V AC 50/60 Hz

    • 2.2 kW at 690 V AC 50/60 Hz

  • Breaking capacity:

    • 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2

    • 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2

    • 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2

    • 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2

    • 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2

  • [Ics] rated service short-circuit breaking capacity:

    • 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2

    • 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2

    • 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2

    • 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2

    • 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2

  • Control type: Push-button

  • [In] rated current: 4 A

  • Thermal protection adjustment range: 2.5…4 A conforming to IEC 60947-2

  • Magnetic tripping current: 74 A

  • [Ith] conventional free air thermal current: 4 A conforming to IEC 60947-2

  • [Ue] rated operational voltage: 690 V AC 50/60 Hz conforming to IEC 60947-2

  • [Ui] rated insulation voltage: 690 V AC 50/60 Hz conforming to IEC 60947-2

  • [Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947-2

  • Phase failure sensitivity: Yes conforming to IEC 60947-4-1

  • Suitability for isolation: Yes conforming to IEC 60947-1

  • Power dissipation per pole: 2.5 W

  • Mechanical durability: 100000 cycles

  • Electrical durability:

    • 100000 cycles for AC-3 at 415 V In

    • 100000 cycles for AC-3e at 415 V In

  • Rated duty: Uninterrupted conforming to IEC 60947-4-1

  • Connections - terminals:

    • Power circuit: screw clamp terminal 2 cable(s) 1…6 mm² - solid

    • Power circuit: screw clamp terminal 2 cable(s) 1.5…6 mm² - flexible without cable end

    • Power circuit: screw clamp terminal 2 cable(s) 1…4 mm² - flexible with cable end

  • Tightening torque: 1.7 N.m - on screw clamp terminal

  • Fixing mode:

    • 35 mm symmetrical DIN rail: clipped

    • Panel: screwed (with adaptor plate)

  • Mounting position:

    • Horizontal

    • Vertical

  • Width: 45 mm

  • Height: 89 mm

  • Depth: 78.5 mm

  • Net weight: 0.26 kg

  • Colour: Dark grey

Environment

  • Standards:

    • EN/IEC 60947-2

    • EN/IEC 60947-4-1

    • UL 60947-4-1

    • CSA C22.2 No 60947-4-1

    • IEC/EN 60335-2-40:Annex JJ

    • IEC/EN 60335-1:Clause 30.2

  • Product certifications:

    • CCC

    • UL

    • CSA

    • EAC

    • ATEX

    • LROS (Lloyds register of shipping)

    • BV

    • RINA

    • DNV-GL

    • UKCA

  • IK degree of protection: IK04

  • IP degree of protection: IP20 conforming to IEC 60529

  • Climatic withstand: conforming to IACS E10

  • Ambient air temperature for storage: -40…80 °C

  • Fire resistance: 960 °C conforming to IEC 60695-2-11

  • Ambient air temperature for operation: -20…60 °C

  • Mechanical robustness:

    • Shocks: 30 Gn for 11 ms

    • Vibrations: 5 Gn, 5...150 Hz

  • Operating altitude: <= 2000 m

Packing Units
Package 1

  • Unit Type of Package: PCE

  • Number of Units: 1

  • Package Height: 4.800 cm

  • Package Width: 8.500 cm

  • Package Length: 9.300 cm

  • Package Weight: 255.000 g

Package 2

  • Unit Type of Package: S02

  • Number of Units: 24

  • Package Height: 15.000 cm

  • Package Width: 30.000 cm

  • Package Length: 40.000 cm

  • Package Weight: 6.414 kg

Package 3

  • Unit Type of Package: P06

  • Number of Units: 384

  • Package Height: 75.000 cm

  • Package Width: 60.000 cm

  • Package Length: 80.000 cm

  • Package Weight: 109.232 kg

  • Performance Curves

  • Thermal-Magnetic Tripping Curves for GV2ME and GV2P

  • Average Operating Times at 20 °C Related to Multiples of the Setting Current

  • 1

  • 3 poles from cold state

  • 2

  • 2 poles from cold state

  • 3

  • 3 poles from hot state

  • Current Limitation on Short-Circuit for GV2ME and GV2P (3-Phase 400/415 V))

  • Dynamic Stress

  • I peak = f (prospective Isc) at 1.05 Ue = 435 V

  • 1

  • Maximum peak current

  • 2

  • 24-32 A

  • 3

  • 20-25 A

  • 4

  • 17-23 A

  • 5

  • 13-18 A

  • 6

  • 9-14 A

  • 7

  • 6-10 A

  • 8

  • 4-6.3 A

  • 9

  • 2.5-4 A

  • 10

  • 1.6-2.5 A

  • 11

  • 1-1.6 A

  • 12

  • Limit of rated ultimate breaking capacity on short-circuit of GV2ME (14, 18, 23, and 25 A ratings).

  • Thermal Limit on Short-Circuit for GV2ME

  • Thermal Limit in kA2s in the Magnetic Operating Zone

  • Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V

  • 1

  • 24-32 A

  • 2

  • 20-25 A

  • 3

  • 17-23 A

  • 4

  • 13-18 A

  • 5

  • 9-14 A

  • 6

  • 6-10 A

  • 7

  • 4-6.3 A

  • 8

  • 2.5-4 A

  • 9

  • 1.6-2.5 A

  • 10

  • 1-1.6 A


Dimensions Drawings
Dimension
GV2ME



(1)
Maximum
X1 Electrical clearance = 40 mm for Ue ≤ 690 V

a b

GV2ME●●

89

GV2ME●●3

101

 

Mounting
GV2ME
On 35 mm rail



c = 78.5 on AM1 DP200 (35 x 7.5)
c = 86 on AM1 DE200, ED200 (35 x 15)
On panel with adapter plate GV2AF02



On pre-slotted plate AM1 PA



On rails DZ5 MB201



GV2AF01
Combination GV2ME + TeSys k contactor



GV2AF3
Combination GV2ME + TeSys d contactor

 

Dimension GV2ME + LC1D09…D18 GV2ME + LC1D25 and D32
b 176.4 186.8
c1 94.1 100.4
c 99.6 105.9


GV2AF4 + LAD311
Combination GV2ME + TeSys d contactor


 
Dimension GV2ME + LC1D09…D18 GV2ME + LC1D25 and D32
b 176.4 186.8
c1 103.1 136.4
c 135.6 141.9
d1 107 107
d 112.5 112.5
 

GV2ME + GV1L3 (Current Limiter)

X1 = 10 mm for Ue = 230 V or 30 mm for 230 V < Ue ≤ 690 V