TeSys GV2-Circuit breaker-thermal-magnetic - 2.5...4 A - screw clamp terminals
GV2ME08
TeSys GV motor circuit breaker, 3 poles (3P), 4A/690V, for 3-phase motor applications 1.1-1.5kW@400V. It provides a thermal-magnetic protection with a thermal setting range 2.5-4A, magnetic tripping at 13xIn, high breaking capacity Icu 100kA@400V. Connection by screw clamp terminals. Start-stop control by push-button guaranteed for 100 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX).
Main
-
Range: TeSys Deca
-
Product name: TeSys GV2
-
Product or component type: Motor circuit breaker
-
Device short name: GV2ME
-
Device application: Motor protection
-
Trip unit technology: Thermal-magnetic
Complementary
-
Poles description: 3P
-
Network type: AC
-
Utilisation category:
-
Category A conforming to IEC 60947-2
-
AC-3 conforming to IEC 60947-4-1
-
AC-3e conforming to IEC 60947-4-1
-
-
Network frequency: 50/60 Hz conforming to IEC 60947-2
-
Motor power kW:
-
1.1 kW at 400/415 V AC 50/60 Hz
-
1.5 kW at 400/415 V AC 50/60 Hz
-
1.5 kW at 500 V AC 50/60 Hz
-
2.2 kW at 500 V AC 50/60 Hz
-
3 kW at 690 V AC 50/60 Hz
-
2.2 kW at 690 V AC 50/60 Hz
-
-
Breaking capacity:
-
100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
-
100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
-
100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
-
100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
-
3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
-
-
[Ics] rated service short-circuit breaking capacity:
-
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
-
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
-
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
-
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
-
75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
-
-
Control type: Push-button
-
[In] rated current: 4 A
-
Thermal protection adjustment range: 2.5…4 A conforming to IEC 60947-2
-
Magnetic tripping current: 74 A
-
[Ith] conventional free air thermal current: 4 A conforming to IEC 60947-2
-
[Ue] rated operational voltage: 690 V AC 50/60 Hz conforming to IEC 60947-2
-
[Ui] rated insulation voltage: 690 V AC 50/60 Hz conforming to IEC 60947-2
-
[Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947-2
-
Phase failure sensitivity: Yes conforming to IEC 60947-4-1
-
Suitability for isolation: Yes conforming to IEC 60947-1
-
Power dissipation per pole: 2.5 W
-
Mechanical durability: 100000 cycles
-
Electrical durability:
-
100000 cycles for AC-3 at 415 V In
-
100000 cycles for AC-3e at 415 V In
-
-
Rated duty: Uninterrupted conforming to IEC 60947-4-1
-
Connections - terminals:
-
Power circuit: screw clamp terminal 2 cable(s) 1…6 mm² - solid
-
Power circuit: screw clamp terminal 2 cable(s) 1.5…6 mm² - flexible without cable end
-
Power circuit: screw clamp terminal 2 cable(s) 1…4 mm² - flexible with cable end
-
-
Tightening torque: 1.7 N.m - on screw clamp terminal
-
Fixing mode:
-
35 mm symmetrical DIN rail: clipped
-
Panel: screwed (with adaptor plate)
-
-
Mounting position:
-
Horizontal
-
Vertical
-
-
Width: 45 mm
-
Height: 89 mm
-
Depth: 78.5 mm
-
Net weight: 0.26 kg
-
Colour: Dark grey
Environment
-
Standards:
-
EN/IEC 60947-2
-
EN/IEC 60947-4-1
-
UL 60947-4-1
-
CSA C22.2 No 60947-4-1
-
IEC/EN 60335-2-40:Annex JJ
-
IEC/EN 60335-1:Clause 30.2
-
-
Product certifications:
-
CCC
-
UL
-
CSA
-
EAC
-
ATEX
-
LROS (Lloyds register of shipping)
-
BV
-
RINA
-
DNV-GL
-
UKCA
-
-
IK degree of protection: IK04
-
IP degree of protection: IP20 conforming to IEC 60529
-
Climatic withstand: conforming to IACS E10
-
Ambient air temperature for storage: -40…80 °C
-
Fire resistance: 960 °C conforming to IEC 60695-2-11
-
Ambient air temperature for operation: -20…60 °C
-
Mechanical robustness:
-
Shocks: 30 Gn for 11 ms
-
Vibrations: 5 Gn, 5...150 Hz
-
-
Operating altitude: <= 2000 m
Packing Units
Package 1
-
Unit Type of Package: PCE
-
Number of Units: 1
-
Package Height: 4.800 cm
-
Package Width: 8.500 cm
-
Package Length: 9.300 cm
-
Package Weight: 255.000 g
Package 2
-
Unit Type of Package: S02
-
Number of Units: 24
-
Package Height: 15.000 cm
-
Package Width: 30.000 cm
-
Package Length: 40.000 cm
-
Package Weight: 6.414 kg
Package 3
-
Unit Type of Package: P06
-
Number of Units: 384
-
Package Height: 75.000 cm
-
Package Width: 60.000 cm
-
Package Length: 80.000 cm
-
Package Weight: 109.232 kg
-
Performance Curves
-
Thermal-Magnetic Tripping Curves for GV2ME and GV2P
-
Average Operating Times at 20 °C Related to Multiples of the Setting Current
-

-
1
-
3 poles from cold state
-
2
-
2 poles from cold state
-
3
-
3 poles from hot state
-
Current Limitation on Short-Circuit for GV2ME and GV2P (3-Phase 400/415 V))
-
Dynamic Stress
-
I peak = f (prospective Isc) at 1.05 Ue = 435 V
-

-
1
-
Maximum peak current
-
2
-
24-32 A
-
3
-
20-25 A
-
4
-
17-23 A
-
5
-
13-18 A
-
6
-
9-14 A
-
7
-
6-10 A
-
8
-
4-6.3 A
-
9
-
2.5-4 A
-
10
-
1.6-2.5 A
-
11
-
1-1.6 A
-
12
-
Limit of rated ultimate breaking capacity on short-circuit of GV2ME (14, 18, 23, and 25 A ratings).
-
Thermal Limit on Short-Circuit for GV2ME
-
Thermal Limit in kA2s in the Magnetic Operating Zone
-
Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V
-

-
1
-
24-32 A
-
2
-
20-25 A
-
3
-
17-23 A
-
4
-
13-18 A
-
5
-
9-14 A
-
6
-
6-10 A
-
7
-
4-6.3 A
-
8
-
2.5-4 A
-
9
-
1.6-2.5 A
-
10
-
1-1.6 A
Dimensions Drawings
Dimension
GV2ME

(1)
Maximum
X1 Electrical clearance = 40 mm for Ue ≤ 690 V
| a | b |
|
GV2ME●● |
89 |
|
GV2ME●●3 |
101 |
Mounting
GV2ME
On 35 mm rail

c = 78.5 on AM1 DP200 (35 x 7.5)
c = 86 on AM1 DE200, ED200 (35 x 15)
On panel with adapter plate GV2AF02

On pre-slotted plate AM1 PA

On rails DZ5 MB201

GV2AF01
Combination GV2ME + TeSys k contactor

GV2AF3
Combination GV2ME + TeSys d contactor

| Dimension | GV2ME + LC1D09…D18 | GV2ME + LC1D25 and D32 |
|---|---|---|
| b | 176.4 | 186.8 |
| c1 | 94.1 | 100.4 |
| c | 99.6 | 105.9 |
GV2AF4 + LAD311
Combination GV2ME + TeSys d contactor

| Dimension | GV2ME + LC1D09…D18 | GV2ME + LC1D25 and D32 |
|---|---|---|
| b | 176.4 | 186.8 |
| c1 | 103.1 | 136.4 |
| c | 135.6 | 141.9 |
| d1 | 107 | 107 |
| d | 112.5 | 112.5 |
GV2ME + GV1L3 (Current Limiter)

X1 = 10 mm for Ue = 230 V or 30 mm for 230 V < Ue ≤ 690 V
Connections and Schema
GV2ME•• and GV2RT

Connection of Undervoltage Trip for Dangerous Machines (Conforming to INRS) on GV2ME Only

Inquiry - Schneider GV2 4A Circuit Breaker Thermal-Magnetic GV2ME08