LADN11
TeSys Deca instantaneous auxiliary contact block, for contactors LC1D, LC1F and control relays CAD. It provides 1NO+1NC contacts (NC mirror certified) rated up to 10A/690V AC, connection by screw clamp terminals. Clip-on front mounting, it procures high reliability and durability. Multi standards certified (IEC, UL, CSA, CCC, EAC), Sustainability compliant.
Main
- Range:
- TeSys
- TeSys Deca
- Product name: TeSys Deca
- Product or component type: Auxiliary contact block
- Device short name: LADN
- Range compatibility:
- TeSys D CAD
- TeSys D LC1D
- TeSys F LC1F
- TeSys F CR1F
- TeSys Deca CAD
- TeSys Deca LC1D
- Mounting location: Front
- Pole contact composition: 1 NO + 1 NC
- Contacts operation: Instantaneous
- [Ue] rated operational voltage: 690 V AC 25...400 Hz
- [Ie] rated operational current:
- 6 A at 120 V AC-15
- 1.04 A at 690 V AC-15
- 0.55 A at 125 V DC-13
- 0.1 A at 600 V DC-13
- [Ui] rated insulation voltage:
- 690 V conforming to IEC 60947-5-1
- 600 V conforming to UL
- 600 V conforming to CSA
- [Ith] conventional free air thermal current: 10 A (at 60 °C)
- Standards:
- EN/IEC 60947-5-1
- GB/T 14048.5
- EN 50012
- UL 60947-5-1
- CSA C22.2 No 60947-5-1
- IEC 60335-1:Clause 30.2
- IEC 60335-2-40:Annex JJ
- UL 60335-2-40:Annex JJ
- Product certifications:
- CB Scheme
- UL
- CSA
- CCC
- EAC
- UKCA
- Irms rated making capacity:
- 140 A AC conforming to IEC 60947-5-1
- 250 A DC conforming to IEC 60947-5-1
- Permissible short-time rating:
- 100 A 60 °C 1 s
- 120 A 60 °C 500 ms
- 140 A 60 °C 100 ms
- Protection type: GG fuse 10 A
- Mechanical durability: 30 Mcycles
- Minimum switching current: 5 mA
- Minimum switching voltage: 17 V
- Non-overlap time:
- 1.5 ms on de-energisation no overlap between NC and NO contact
- 1.5 ms on energisation no overlap between NC and NO contact
- Insulation resistance: > 10 MOhm
- Connections - terminals:
- Screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
- Screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
- Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
- Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
- Screw clamp terminals 1 cable(s) 1…4 mm²rigid without cable end
- Screw clamp terminals 2 cable(s) 1…4 mm²rigid without cable end
- Tightening torque:
- 1.7 N.m - with screwdriver flat Ø 6 mm
- 1.7 N.m - with screwdriver Philips No 2
- 1.7 N.m - with screwdriver pozidriv No 2
- Height: 48 mm
- Width: 26 mm
- Depth: 42 mm
- Colour: Dark grey
- Environmental characteristic: Normal environment
- IP degree of protection: IP20 conforming to IEC 60529
- Protective treatment: TH conforming to IEC 60068
- Ambient air temperature for storage: -60…80 °C
- Ambient air temperature for operation: -5…60 °C
- Operating altitude: 3000 m
Package 1
- Unit Type of Package: PCE
- Number of Units: 1
- Package Height: 3 cm
- Package Width: 4.2 cm
- Package Length: 5.3 cm
- Package Weight: 34 g
- Unit Type of Package: S03
- Number of Units: 320
- Package Height: 30 cm
- Package Width: 30 cm
- Package Length: 40 cm
- Package Weight: 11.452 kg
- Unit Type of Package: P06
- Number of Units: 2560
- Package Height: 75 cm
- Package Width: 60 cm
- Package Length: 80 cm
- Package Weight: 99 kg