TeSys GV2-Circuit breaker-thermal-magnetic - 2.5...4 A - screw clamp terminals
GV2ME08

TeSys GV motor circuit breaker, 3 poles (3P), 4A/690V, for 3-phase motor applications 1.1-1.5kW@400V. It provides a thermal-magnetic protection with a thermal setting range 2.5-4A, magnetic tripping at 13xIn, high breaking capacity Icu 100kA@400V. Connection by screw clamp terminals. Start-stop control by push-button guaranteed for 100 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX).
Main

  • Range: TeSys Deca

  • Product name: TeSys GV2

  • Product or component type: Motor circuit breaker

  • Device short name: GV2ME

  • Device application: Motor protection

  • Trip unit technology: Thermal-magnetic

Complementary

  • Poles description: 3P

  • Network type: AC

  • Utilisation category:

    • Category A conforming to IEC 60947-2

    • AC-3 conforming to IEC 60947-4-1

    • AC-3e conforming to IEC 60947-4-1

  • Network frequency: 50/60 Hz conforming to IEC 60947-2

  • Motor power kW:

    • 1.1 kW at 400/415 V AC 50/60 Hz

    • 1.5 kW at 400/415 V AC 50/60 Hz

    • 1.5 kW at 500 V AC 50/60 Hz

    • 2.2 kW at 500 V AC 50/60 Hz

    • 3 kW at 690 V AC 50/60 Hz

    • 2.2 kW at 690 V AC 50/60 Hz

  • Breaking capacity:

    • 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2

    • 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2

    • 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2

    • 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2

    • 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2

  • [Ics] rated service short-circuit breaking capacity:

    • 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2

    • 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2

    • 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2

    • 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2

    • 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2

  • Control type: Push-button

  • [In] rated current: 4 A

  • Thermal protection adjustment range: 2.5…4 A conforming to IEC 60947-2

  • Magnetic tripping current: 74 A

  • [Ith] conventional free air thermal current: 4 A conforming to IEC 60947-2

  • [Ue] rated operational voltage: 690 V AC 50/60 Hz conforming to IEC 60947-2

  • [Ui] rated insulation voltage: 690 V AC 50/60 Hz conforming to IEC 60947-2

  • [Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947-2

  • Phase failure sensitivity: Yes conforming to IEC 60947-4-1

  • Suitability for isolation: Yes conforming to IEC 60947-1

  • Power dissipation per pole: 2.5 W

  • Mechanical durability: 100000 cycles

  • Electrical durability:

    • 100000 cycles for AC-3 at 415 V In

    • 100000 cycles for AC-3e at 415 V In

  • Rated duty: Uninterrupted conforming to IEC 60947-4-1

  • Connections - terminals:

    • Power circuit: screw clamp terminal 2 cable(s) 1…6 mm² - solid

    • Power circuit: screw clamp terminal 2 cable(s) 1.5…6 mm² - flexible without cable end

    • Power circuit: screw clamp terminal 2 cable(s) 1…4 mm² - flexible with cable end

  • Tightening torque: 1.7 N.m - on screw clamp terminal

  • Fixing mode:

    • 35 mm symmetrical DIN rail: clipped

    • Panel: screwed (with adaptor plate)

  • Mounting position:

    • Horizontal

    • Vertical

  • Width: 45 mm

  • Height: 89 mm

  • Depth: 78.5 mm

  • Net weight: 0.26 kg

  • Colour: Dark grey

Environment

  • Standards:

    • EN/IEC 60947-2

    • EN/IEC 60947-4-1

    • UL 60947-4-1

    • CSA C22.2 No 60947-4-1

    • IEC/EN 60335-2-40:Annex JJ

    • IEC/EN 60335-1:Clause 30.2

  • Product certifications:

    • CCC

    • UL

    • CSA

    • EAC

    • ATEX

    • LROS (Lloyds register of shipping)

    • BV

    • RINA

    • DNV-GL

    • UKCA

  • IK degree of protection: IK04

  • IP degree of protection: IP20 conforming to IEC 60529

  • Climatic withstand: conforming to IACS E10

  • Ambient air temperature for storage: -40…80 °C

  • Fire resistance: 960 °C conforming to IEC 60695-2-11

  • Ambient air temperature for operation: -20…60 °C

  • Mechanical robustness:

    • Shocks: 30 Gn for 11 ms

    • Vibrations: 5 Gn, 5...150 Hz

  • Operating altitude: <= 2000 m

Packing Units
Package 1

  • Unit Type of Package: PCE

  • Number of Units: 1

  • Package Height: 4.800 cm

  • Package Width: 8.500 cm

  • Package Length: 9.300 cm

  • Package Weight: 255.000 g

Package 2

  • Unit Type of Package: S02

  • Number of Units: 24

  • Package Height: 15.000 cm

  • Package Width: 30.000 cm

  • Package Length: 40.000 cm

  • Package Weight: 6.414 kg

Package 3

  • Unit Type of Package: P06

  • Number of Units: 384

  • Package Height: 75.000 cm

  • Package Width: 60.000 cm

  • Package Length: 80.000 cm

  • Package Weight: 109.232 kg

  • Performance Curves

  • Thermal-Magnetic Tripping Curves for GV2ME and GV2P

  • Average Operating Times at 20 °C Related to Multiples of the Setting Current

  • 1

  • 3 poles from cold state

  • 2

  • 2 poles from cold state

  • 3

  • 3 poles from hot state

  • Current Limitation on Short-Circuit for GV2ME and GV2P (3-Phase 400/415 V))

  • Dynamic Stress

  • I peak = f (prospective Isc) at 1.05 Ue = 435 V

  • 1

  • Maximum peak current

  • 2

  • 24-32 A

  • 3

  • 20-25 A

  • 4

  • 17-23 A

  • 5

  • 13-18 A

  • 6

  • 9-14 A

  • 7

  • 6-10 A

  • 8

  • 4-6.3 A

  • 9

  • 2.5-4 A

  • 10

  • 1.6-2.5 A

  • 11

  • 1-1.6 A

  • 12

  • Limit of rated ultimate breaking capacity on short-circuit of GV2ME (14, 18, 23, and 25 A ratings).

  • Thermal Limit on Short-Circuit for GV2ME

  • Thermal Limit in kA2s in the Magnetic Operating Zone

  • Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V

  • 1

  • 24-32 A

  • 2

  • 20-25 A

  • 3

  • 17-23 A

  • 4

  • 13-18 A

  • 5

  • 9-14 A

  • 6

  • 6-10 A

  • 7

  • 4-6.3 A

  • 8

  • 2.5-4 A

  • 9

  • 1.6-2.5 A

  • 10

  • 1-1.6 A


Dimensions Drawings
Dimension
GV2ME



(1)
Maximum
X1 Electrical clearance = 40 mm for Ue ≤ 690 V

a b

GV2ME●●

89

GV2ME●●3

101

 

Mounting
GV2ME
On 35 mm rail



c = 78.5 on AM1 DP200 (35 x 7.5)
c = 86 on AM1 DE200, ED200 (35 x 15)
On panel with adapter plate GV2AF02



On pre-slotted plate AM1 PA



On rails DZ5 MB201



GV2AF01
Combination GV2ME + TeSys k contactor



GV2AF3
Combination GV2ME + TeSys d contactor

 

Dimension GV2ME + LC1D09…D18 GV2ME + LC1D25 and D32
b 176.4 186.8
c1 94.1 100.4
c 99.6 105.9


GV2AF4 + LAD311
Combination GV2ME + TeSys d contactor


 
Dimension GV2ME + LC1D09…D18 GV2ME + LC1D25 and D32
b 176.4 186.8
c1 103.1 136.4
c 135.6 141.9
d1 107 107
d 112.5 112.5
 

GV2ME + GV1L3 (Current Limiter)

X1 = 10 mm for Ue = 230 V or 30 mm for 230 V < Ue ≤ 690 V

Connections and Schema
GV2ME•• and GV2RT



Connection of Undervoltage Trip for Dangerous Machines (Conforming to INRS) on GV2ME Only



 

 

Specifications

Sorry, currently do not have any product specifications
Sorry, currently do not have any video uploaded.
Sorry, currently do not have any file for download.